Modern industrial building with gray and pink facades, featuring louvre and multiple chimneys against a clear blue sky.

Understanding louvre airflow performance

When specifying louvres, one of the first considerations is how effectively it will allow air to flow through and ventilate a space. One metric which is sometimes assumed to measure this is the “free area” (also known as the “percentage free area” or “open area”) of the louvre. This represents the total unobstructed area of a louvre through which air can flow. In practice, however, this metric ignores a number of factors which can significantly impact the flow of air. This means louvres with the same “free area” measurement can actually allow very different airflow rates to internal spaces.

In this article, we explore:

  • the limitations of “free area”,
  • the importance of pressure drop, and
  • why aerodynamic efficiency (Cv) and Airflow Class are better indicators of airflow performance.

Why “free area” shouldn’t be used when specifying louvres

The “free area” for a louvre is typically calculated by multiplying the sum of the minimum distance between the intermediate blades, top blade, head and bottom blade and the cill by the minimum distance between the jambs. The “free area” is then presented as a percentage of the total area.

There are a number of drawbacks to this approach:

  • Number of banks is not considered — “free area” calculations do not account for the number of banks of blades within a louvre unit. Colt International offer louvres in up to three banks for enhanced rain defence. However, increasing the number of banks can have a significant impact on the volume of airflow through a unit.
  • Blade shape and angle not fully considered — the “free area” calculation does not fully account for how the specific pitch or surface shape of the unit blades may affect airflow.
  • Figure may be based on standard dimensions — the “free area” value is often based on a theoretical 1m x 1m unit. In practice, the actual unit dimensions may be very different from this. This can have a notable impact on the actual “free area” particularly for smaller units where a greater proportion of area will be taken up by the frame.

As a result, the “free area” tells specifiers very little about the actual volume of airflow that can be expected through a unit. It should therefore not be used in specifications.

To get a better understanding of airflow through a louvre, we need to instead look at its aerodynamic effectiveness and how this affects the pressure drop through the unit.

Why aerodynamic effectiveness and pressure drop matter for louvres

Pressure drop is the difference between the air pressure at the point of entering and exiting the louvre. A higher pressure drop value (measured in Pascals) indicates that there is greater resistance to air flowing through the louvre, meaning a lower air flow into the internal space.

Factors which can influence the pressure drop through a unit include:

  • The number of blade banks — increasing the number of banks of blades within a louvre will provide additional rain defence, however, this comes at the cost of additional air resistance.
  • The pitch of blades — increasing the pitch of louvre blades can help to prevent rain from passing through the louvre but will again increase the air resistance and pressure drop.
  • The shape and surface of blades — much like the wings of an aircraft, the form of blades can be carefully shaped to limit air resistance and improve the flow of air through a unit.
  • Other internal components and framing — elements such as intermediate mullions and rear framing can add additional air resistance.
  • Bird or insect screens — the screens and supports used to prevent insects or birds can also add additional resistance to air flow.

To provide a clear assessment of how these different factors can impact the pressure drop through a unit (and consequently the rate of airflow), BS EN 13030: 2021 sets out a process for testing and classifying the aerodynamic coefficient (Cv) for the louvre. This value essentially measures the aerodynamic effectiveness of a unit. A higher aerodynamic coefficient indicates that a unit will be less resistant to air passage, resulting in a reduced pressure drop and improved air flow to the internal space.

How the aerodynamic coefficient (Cv) of a louvre is calculated in BS EN 13030

The test described within BS EN 13030 to measure the aerodynamic performance of a louvre involves the unit being mounted within a wind tunnel and its resistance to airflow measured against that of a known opening plate at varying airflow velocities. Values are measured with the louvres as both air intake and discharge and an aerodynamic coefficient for both is then calculated based on these measurements and the face area (the total area within the front frame of the louvre).

To allow specifiers to compare between different louvre products and configurations, a standard sized unit (1m x 1m) is used for the test.

Based on their aerodynamic coefficient, the standard then classifies the louvre into one of four Airflow Classes:

ClassAerodynamic Coefficient
Class 10.400 and above
Class 20.300 to 0.399
Class 30.200 to 0.299
Class 40.199 and below

The standard also specifies a testing configuration to assess rain defence using water spray at 75 mm/hr and wind at 30 mph and a suction velocity through the louvre ranging from 0 to 3.5 m/s. This test allows the classification of louvres from A (best) to D (worst) at different suction velocities based on how much rainwater passes through the unit.

Both tests need to be repeated for all different configurations to adjust for how factors such as blade pitch, the number of blade banks and presence of insect or bird screens may impact aerodynamic performance.

The Airflow Classes above provide a quick reference point for specifiers looking to understand how well a particular louvre may allow airflow to internal spaces. The specific Cv figure can then be used to calculate the minimum area of the chosen louvre needed to provide the required internal airflow and pressure difference.

Can Colt provide aerodynamic performance ratings for its louvres?

Yes, all our louvre products and common configurations have been tested and classified under BS EN 13030. Our dedicated louvre team can work with specifiers to find the optimal solution, allowing you to achieve the best balance of airflow and rain defence to meet your project goals.