How do fire and smoke dampers work

September 2026

Fire and smoke dampers are louvered vents or shutters which are used within ductwork and are designed to automatically close or open in the event of a fire, limiting the spread of flames and controlling the movement of smoke and toxic gases. They play a critical role in supporting building compartmentation and allowing safe evacuation in the event of a fire.

What is the difference between fire and smoke dampers?

Fire and smoke dampers play separate but important functions in protecting occupants in the event of a fire:

  • Fire dampers are open in normal use, permitting the flow of air through the ductwork. When a fire is detected, they automatically shut to act as a barrier which prevents the spread of flame up to the specified fire resistance of the damper.
  • Smoke dampers are designed to control the flow of smoke and hot gases through a smoke control system. In the event of a fire, smoke dampers in the immediate area will open, allowing smoke and hot gases to flow into the smoke control system. All other smoke dampers will close to prevent the toxic gases from escaping out of the system into other areas of a building.
  • Smoke and fire dampers are designed and tested to both resist fire and limit the passage of smoke and toxic gases when closed.

How are fire dampers controlled?

Fire dampers are designed to spring closed. They can either be controlled with a fusible link which will melt at a specified temperature or by using a motorised mechanism. The motorised approach offers notable benefits as it allows dampers to be reopened from a central control point rather than having to be physically accessed.

How are fire dampers tested and classified?

Mechanical fire dampers are tested to BS EN 1366-2 – Fire resistance tests for fire dampers. The results from this testing are classified in accordance with BS EN 13501-3:2025 - Fire classification of construction products and building elements. Standard fire dampers will be classified against the following criteria:

  • Integrity (E) — marking their ability to prevent the passage of smoke and hot gases to the unexposed side of the unit.
  • Insulation (I) — marking their ability to limit the spread of heat to the unexposed side of the unit.
  • Time rating — the time period they are able to sustain both E and I.
  • Orientation — marking the intended installation orientation – Vertical (ve) or Horizontal (ho)
  • Smoke leakage (S) — marking the units’ ability to restrict smoke and hot gasses. This is only applicable for smoke and fire dampers.

It is a legal requirement for all fire dampers to be CE or UKCA marked via BS EN 15650: 2010 - Ventilation for buildings. Fire dampers.

How are smoke dampers controlled?

Smoke control dampers typically open and close using automatic electric or pneumatic actuators. These are usually linked to the fire and smoke detection systems via a central control panel. When a fire is detected, this control system will order the smoke dampers in the immediate area to open — drawing smoke and hot gases into the smoke control system. All other smoke dampers remain closed to prevent these toxic gases escaping into other areas of the building. This procedure is typically preprogrammed as part of a detailed cause and effect strategy.

What is the difference between single compartment and multi-compartment smoke dampers?

As their name suggests, single compartment smoke dampers are designed to be used within an individual fire compartment. In contrast, multi-compartment smoke dampers are designed for use as part of the barrier between compartments. For this reason, single compartment dampers are only assigned a temperature rating (E) whilst multi-compartment units must achieve a designated fire resistance rating (EI). Multi-compartment dampers can also be used anywhere within the compartment.

How are smoke dampers tested and classified?

All smoke dampers should be tested to BS EN 1366-10: 2022 – Fire resistance tests for smoke control dampers and classified in accordance with BS EN 13501-4: 2016 - Fire classification of construction products and building elements. Additional testing may also be carried out to BS EN 1366-2 – Fire resistance tests for fire dampers and classified in accordance with BS EN 13501-3:2025 - Fire classification of construction products and building elements.

As with fire dampers, these units will typically be classified for:

  • Integrity (E) — for single compartment units, this will be listed as a subscript 600 indicating the rating is limited to 600°C for smoke and hot gases.
  • Insulation (I) — multi-compartment only
  • Time rating
  • Orientation
  • Smoke leakage (S)

Additionally, they will be assigned the following:

  • Testing direction — indicating if it is tested from inside to out (i→o), from outside to in (o→i), or both (i↔o). Multi-compartment must be tested for both.
  • Operating pressure — indicates the pressure level it is tested for in general use.
  • Number of test cycles (C) — indicates the number of cycles the damper is tested to.
  • Manual or automatic operation — indicates if the unit is activated manually (MA) or automatically (AA)
  • Single or Multi compartment — indicates if it is a single compartment (Single) or Multi-compartment (Multi) damper.

Again, it is a legal requirement for all smoke dampers to be CE or UKCA marked via BS EN 12101-8: 2021 - Smoke and heat control systems - Smoke control dampers.

Specifying fire and smoke dampers for your project

Colt International offer a wide range of smoke and fire dampers to meet your project requirements. Our experienced design team can work with you to develop a tailored smoke control system design for your project, incorporating suitable dampers to ensure your building is fully compliant and safeguards occupants. Contact us below to discuss your project.